How to Calculate the Required Servo Stabilizer Capacity
Servo stabilizers are normally specified in kVA. Calculate the simultaneous apparent power, then check starting demand and the manufacturer’s operating limits.
Calculate running kVA
For a single-phase load: kVA = V × I / 1000. For a balanced three-phase load: kVA = √3 × line voltage × line current / 1000. If electrical input kW and power factor are known, kVA = kW / PF. Motor shaft kW must first be divided by efficiency to estimate electrical input kW.
Worked example
A balanced load drawing 100 A at 415 V requires approximately 71.9 kVA. An illustrative 20% allowance gives 86.3 kVA before selecting a supported rating. This allowance is an example, not a universal sizing rule.
Check transient and input conditions
Add only loads expected to operate together, allow for agreed future expansion and verify starting current, duration and permitted voltage dip. Confirm full output capacity at the lowest input voltage and site temperature with the supplier.
Frequently asked questions
What information should I provide for a project recommendation?
Share the equipment datasheets, load or string schedule, installation conditions and single-line diagram. Confirm the proposed configuration with the project electrical designer.
Are the examples a GEESYS product specification?
No. Worked examples explain selection principles. Use the selected product datasheet and approved project design for actual ratings and installation requirements.
Related GEESYS products
Discuss your project with GEESYS
Share your load details, site conditions and single-line diagram for a project-specific recommendation.
Explore related products | Contact GEESYSRelated technical guides
- How to Select a Servo Voltage Stabilizer for Industrial Loads
- What Is an APFC Panel and How Does It Work?
- How to Select the Right APFC Panel for an Industry
- Online UPS vs Servo Stabilizer: What Is the Difference?